Ubetinget kortslutningssikker transformatorer!!!

De standart transformatorer man typisk bruger, som er <= 3VA, er stemplet til at være ubetinget kortslutningssikker.
DET HOLDER IKKE HELT.

Det gælder kun hvis temperaturen ikke er alt for høj.
Forneden ses en beskrivelse fra Hahn om problemet på en BV EI 306 3367.

The temperatur ambient 80 degree is no problem at load 100 mA. At full load (200 mA) the heating of the transformer is 34 degree, absolute temperature 80 + 34 = 114 °C (maximum in accordance with EN 61558 Insulation Class F is 140°C). But there is a heating problem at short circuit. In this case the heating is 116 degree, absolute temperature 80 + 116 = 196°C (maximum in accordance with EN 61558 Insulation Class F is 190°C). You need a fuse to make the transformer short circuit proof in your application!

Keywords:
Trafo, Transformer, overbelastning, varme, temperatur, kortslutningssikker, problem, isolation.